Mechanical Connection Of The Cabinet Units; Connection Of The Cooling Circuit Collecting Pipes - Siemens SINAMICS S120 Manual

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.3.5

Mechanical connection of the cabinet units

3.3.5.1

Connection of the cooling circuit collecting pipes

Description
The collecting pipes of the cooling circuit must be connected during the installation of the
cabinet units or transport units. The collecting pipes are located at the rear lower cabinet
area.
The pipe couplings to connect the collecting pipes are included when shipped in the
accessory kits of the cabinet unit. The pipe couplings are called "PLAST-GRIP". The
collecting pipes are covered with protective covers that must be removed prior to installation.
The connection locations must be stabilized using support rings to ensure that the plastic
collecting pipes are adequately connected and stable. The support rings are already
mounted in the factory.
Figure 3-12
Connecting the collecting pipes
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Mechanical installation
3.3 Installing
57