Siemens SINAMICS S120 Manual page 203

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 6- 34
Technical data of the Heat Exchanger Modules, line voltage 3 AC 660 ... 690 V
Article No.
Deionized water circuit in the converter
Cooling power
Intake temperature
- min.
- max:
- <IP55
- IP55
Intake pressure
- min
- max
Rated flow rate
2)
Volume of liquid
Connection, intake/return
- nominal diameter
- outer diameter
Plant-side raw water circuit
Intake temperature
- min.
- max:
- <IP55
- IP55
Intake pressure, max.
Rated flow rate
2)
Pressure drop at the rated flow rate
Connection, intake/return
- nominal diameter
- outer diameter
General data
Supply voltages
- line voltage
- line frequency
- electronics power supply
Current drain
- total operating current 3 AC 690 V, 50/60 Hz
- max. starting current
- electronics current (24 V DC)
Power consumption, max., 3 AC 690 V,
50/60 Hz
Power loss, max., dissipated to the ambient air
4)
Sound pressure level L
pA
Material of the integrated heat exchanger
Degree of protection (standard version)
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
6SL3705-
kW
°C
°C
°C
bar
bar
l/min
dm³
mm
°C
°C
°C
bar
l/min
kPa
mm
V
Hz
V
A
A
A
kW
kW
(1 m) at 50/60 Hz
dB(A)
0RG23-
2AA3
32
1)
45
40
1.7
6.0
88
18
DN32
42.2
5
3)
38
33
6.0
132
50
DN32
42.2
3 AC 660 -10 % ... 3 AC 690 +10 %
ACrms
DC
1.8/2.7
87.7
1.0
1.3/1.7
0.5
<65
Stainless
steel
IP21
Cabinet Modules
6.4 Heat Exchanger Modules
0RG24-
0RG27-
8AA3
2AA3
48
72
1)
1)
45
45
40
40
1.7
1.7
6.0
6.0
132
197
25
43
DN40
DN50
48.3
60.3
5
5
3)
3)
38
38
33
33
6.0
6.0
198
263
60
70
DN40
DN50
48.3
60.3
50 Hz
24 (20.4 ... 28.8)
2.2/3.9
5.2/4.7
87.7
87.7
1.0
1.0
1.7/2.4
4.2/4.2
0.5
0.5
<65
<65
Stainless
Stainless
steel
steel
IP21
IP21
0RG31-
1AA3
110
1)
45
40
1.7
6.0
267
47
DN50
60.3
5
3)
38
33
6.0
445
90
DN65
76.1
5.2/4.7
87.7
1.0
4.2/4.2
0.5
<65
Stainless
steel
IP21