Siemens SINAMICS S120 Manual page 36

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System overview
2.9 System data
Ambient conditions
Ambient temperature
Relative humidity
(condensation not permissible)
corresponds to class
Installation altitude
Deviations from the specified class are shown in
2)
Mechanical strength
Vibrational load
- Displacement
- Acceleration
- Corresponds to class
Shock load
- Acceleration
- Corresponds to class
Deviations from the specified class are shown in
3)
NOTICE
Damage to the device through incorrect storage and transport of liquid-cooled devices
The storage and transport of liquid-cooled devices that have not been completely emptied
can result in damage to the device through freezing.
• Always empty the liquid-cooled devices completely before storage or transport.
Note
Weight of a cabinet unit
The relevant weight of a cabinet unit is specified on the test certificate supplied and on the
rating plate. The specified weight corresponds to the actual expansion stage of the cabinet
unit.
Note
Limiting overvoltages
On systems with a grounded phase conductor and a line voltage > 600 VAC, line-side
components should be installed to limit overvoltages to overvoltage category II according to
EN 61800-5-1.
36
During storage
-25° C to +55° C
5 %
... 95 %
2)
2)
1K4 acc. to EN 60721-3-1
up to 2000 m above sea level - no derating,
> 2000 m - see characteristics/derating data
italics
.
During storage
5 Hz
1.5 mm at
... 9 Hz
3)
5 m/s² at >9 ... 200 Hz
1M2 acc. to EN 60721-3-1
40 m/s
for 22 ms
2
1M2 acc. to EN 60721-3-1
italics
.
During transport
-25° C to +70° C
-40° C
from
for 24 hours
2)
5 % ... 95 % at 40 °C
2K3 acc. to EN 60 721-3-2
During transport
5 Hz
3.1 mm at
... 9 Hz
3)
10 m/s² at >9 ... 200 Hz
2M2 acc. to EN 60721-3-2
100 m/s
for 11 ms
2
2M2 acc. to EN 60721-3-2
During operation
0 °C
... +45 °C
2)
to +50 °C see derating data
95 %
5 % ...
2)
3K3 acc. to EN 60721-3-3
During operation
0.075 mm at 10 ... 58 Hz
9.8 m/s² at >58 ... 200 Hz
-
100 m/s
for 11 ms
2
3M4 acc. to EN 60721-3-3
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A

Advertisement

Table of Contents
loading