Line/Load Connection - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.4.3.1

Line/load connection

Wideband Line Filters for Active Line Modules are designed for a voltage range from
3-ph. 380 V AC -10% (-15% <1 min) up to 3-ph. 480 V AC +10% at 47 Hz to 63 Hz.
Table 2-5
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Wideband Line Filter for Active Line Modules
16 kW
36 and 55 kW
80 kW
120 kW
1) for ring cable lugs to DIN 46234
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
Designations
L1, L2, L3, PE
U, V, W
Screw terminal: 10 mm
3–pin/1.5 Nm (see Screw Terminals)
2
Ground stud: M5/3 Nm
1)
Screw terminal: 50 mm
3–pin/6 Nm (see Screw Terminals)
2
Ground stud: M8/13 Nm
1)
Screw terminal: 95 mm
3–pin/15 Nm (see Screw Terminals)
2
Ground stud: M8/13 Nm
1)
Connection strap: d = 11 mm (M10/25 Nm)
Ground stud: M8/13 Nm
1)
Note: No shock-hazard protection (IP00B acc. to 60529)
2.4 Wideband Line Filter for Active Line Modules
Line Connection Booksize
2-11