Warning
Cable shields and unused power cable conductors (e.g. brake conductors) must be
connected to PE potential to prevent capacitive cross-talk charges.
Non-observance can cause lethal shock voltages.
Caution
Only cables from Siemens must be used for DRIVE-CLiQ connections.
Caution
Connecting cables to temperature sensors must always be installed with shielding. The
cable shield must be connected to the chassis potential at both ends over a large surface
area. Temperature sensor cables that are routed together with the motor cable must be
twisted in pairs and shielded separately.
Notice
The external air cooling can cause the fans and the heat sink to become heavily
contaminated, which may trigger the temperature monitor in the power unit. The fans and
heat sink must be checked for contamination at regular intervals and, if necessary, cleaned.
Note
After installation, the seal on the rear of the device must be checked to ensure that it is tight.
Additional sealing can be used, if necessary.
Note
The mounting frames can only be used if the cabinet has an unpainted metal surface.
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
Motor Modules Booksize
4.3 Motor Module with external air cooling
4-27