Modbus Command Parameters - Siemens SENTRON 7KT1681 Manual

Table of Contents

Advertisement

Commissioning
6.4 Modbus address register for devices with Modbus interface
6.4.2

Modbus command parameters

Modbus function code 06
Address
WORDS
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2FF0H
1
2F01H
1
After executing this command, it is recommended that you issue the REBOOT command.
1)
After executing this command, you can use query 4 under address 0x1F20 to obtain the test result. The bit assignments
2)
are shown in the wiring test results table below.
Wiring test results
The wiring is correct if the result is 0 or no bit is active.
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
56
Measured variables
Reset HI-LO values
Reset max. average values
Reset partial energy
Reset partial hour counter
Reset energy tariffs
Reset alarms
Reset limits
Reset energy total
Reset all hour counters
Factory setting
Save parameters
Load parameters
Wiring test
Reset HI
Reset LO
Measured variable
Voltage L1 - N
Voltage L2 - N
Voltage L3 - N
Current N - L1
Current N - L2
Current N - L3
Incorrect phase sequence
Phase unbalance
Current transformer 1 inverted
Current transformer 2 inverted
Current transformer 3 inverted
Current transformer 1 on phase L2
Current transformer 1 on phase L3
Current transformer 1 on phase L1
UNIT
FORMAT
0
Unsigned int
1
Unsigned int
2
Unsigned int
3
Unsigned int
6
Unsigned int
7
Unsigned int
11
Unsigned int
12
Unsigned int
13
Unsigned int
1)
14
Unsigned int
1)
15
Unsigned int
1)
16
Unsigned int
2)
100
Unsigned int
200
Unsigned int
1
Unsigned int
Manual, 08/2018, 2514284149-01