M09 Alarms (ALAn, n = 1 ... 4)
Note
This menu is divided into 4 sections for alarms ALA1 ... 4.
P09.n.01
P09.n.02
P09.n.03
P09.n.04
P09.n.05
P09.n.01
P09.n.02
P09.n.03
P09.n.04
7KT multimeter
Manual, 08/2018, 2514284149-01
Alarm source
Channel number (n)
Reset mode
Priority
Text
Signal which triggers the alarm when a threshold value (LIMx) is exceeded.
Channel number (n), with reference to the previous parameter.
• ON: You must manually save and reset the alarm.
• OFF: The alarm is saved and reset automatically.
• High: In the event of an alarm, the display automatically switches to the
alarm page and displays the alarm icon.
• Low: In the event of an alarm, the "Information" icon is displayed; the
display does not change.
3.4 Parameterization
Default
Range
OFF
OFF
•
LIMx
•
1
1 ... 4
OFF
OFF
•
ON
•
Low
Low
•
High
•
ALAn
(Freely definable text for alarm.
Max. 16 characters)
Description
35