Huawei FusionModule 1000A40 Maintenance Manual page 94

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Materials: spare water sensor
Document: monitoring device layout diagram
Skill requirement: weak-current engineer
Procedure
Step 1 Locate the water sensor to be replaced based on the alarm information on the monitoring
software terminal.
Figure 5-12 Point-type water sensor
Step 2 Remove the captive screws from the faulty water sensor using a Phillips screwdriver, and
remove the water sensor.
Figure 5-13 Removing a point-type water sensor
Issue 04 (2018-01-05)
For the diagrams, see the initial configuration parameter manual for the solution in use.