Local Fire Emergency Operations (Ce) - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Step 6 Check the cable connection between the extinguishant control panel and the management
system.
Step 7 Check the alarm settings for the extinguishant control panel in the management system.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

6.11 LOCAL FIRE Emergency Operations (CE)

Prerequisites
The management system reports a LOCAL FIRE alarm.
Procedure
Step 1 Locate the alarm or alarm area in the management system.
Step 2 Check the situation inside the pre-fab. module in the video surveillance system.
Step 3 Check whether extinguishant has been released.
Issue 04 (2018-01-05)
Replace the smoke detector if the extinguishant control panel reports a FIRE RELAY
alarm or smoke alarm but the VESDA does not report any alarm.
Replace the heat detector if the extinguishant control panel reports a FIRE RELAY alarm
or heat detector alarm but the management system does not report any overtemperature
alarm.
If the extinguishant control panel does not report any FIRE RELAY, go to
If the extinguishant control panel reports a LOCAL FIRE alarm, refer to the section
"LOCAL FIRE Emergency Operations (CE)".
If the cable connection is correct and the alarm disappears, the troubleshooting ends.
If the cable connection is correct but the alarm persists, go to
If the settings are correct and the alarm disappears, the troubleshooting ends.
If the settings are correct but the alarm persists, contact Huawei technical support.
The following LOCAL FIRE emergency operations are for reference only.
If you find a LOCAL FIRE alarm when working inside a pre-fab. module, determine
whether to extinguish the fire or evacuate the area immediately based on the actual
situation, and contact the personnel on duty or fire engineer promptly.
If the situation inside the pre-fab. module is normal, go to
If onsite fire is confirmed, go to