Monitoring System - Huawei FusionModule 1000A40 Maintenance Manual

Hide thumbs Also See for FusionModule 1000A40:
Table of Contents

Advertisement

FusionModule1000A40 IT Solution
Maintenance Guide (2016.05, AI Version)
Item
Transforme
r output
voltage
inside the
electric
control box
Cables
T/H sensors

3.4.3 Monitoring System

Table 3-18 Semi-annual maintenance checklist for the monitoring system
Item
LAN switch
power
indicator
(PWR).
Issue 04 (2018-01-05)
Method
Measure the output
voltage of the
internal
transformer.
Check cables.
Check the T/H
sensors.
Remove the electric control box before maintaining components inside it.
Method
Check the
indicator.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshooting
The output
If the output voltage is abnormal,
voltage is normal
replace the transformer.
(AC 24 V± 10%)
No cable has
Replace aged cables.
aged.
The T/H sensor
If the reading of a T/H sensor is
reading is normal
inaccurate, check and calibrate
and precise.
the T/H sensor using a
temperature and humidity
measuring instrument with
higher precision.
Expected
Troubleshooting
Result
The PWR
If the indicator is off, check the
indicator is
power supply. Replace the LAN
steady green.
Switch if the power supply is
normal.
If the red indicator is steady on:
1. Check whether two PSUs are
2. Check that the power supply
3. Replace the LAN Switch if
Replace the LAN Switch if the
orange indicator is steady on.
3 Maintenance
configured, and switch on the
power supply.
is switched on.
the power supply to the board
and the PoE power supply are
faulty.
30