FusionModule500 Smart Mini Data Center
User Manual (ECC800e)
Figure 2-82 Wiring diagram for the batteries and the circuit breaker
(1) To a UPS
Step 4 Reinstall the circuit breaker panel on the cabinet and close the cabinet door.
----End

2.3.2.6 (Optional) Connecting Cables Between Battery Packs and the UPS

Figure 2-83
packs.
Issue 07 (2019-12-20)
(2) To a battery string
The figure above is for reference only. If the neutral wire is configured for the battery cabinet, the
neutral wire does not need to be connected.
Cables:
Wire, 450 V/750 V-60227 IEC 02(RV)-10 mm
Wire, 450 V/750 V-60227 IEC 02(RV)-10 mm
Terminal option: The battery cabinet adopts OT terminals. The 10 kVA UPS adopts 10 mm
terminals. The 6 kVA UPS adopts 6 mm
shows cable connections between a 3 kVA, 6 kVA, or 10 kVA UPS and battery
Copyright © Huawei Technologies Co., Ltd.
(3) To a ground point
2
, black, 62 A.
2
, red, 62 A.
2
M4 OT terminals.
2 Installation
2
M6 OT
85