User Manual (ECC800e)
Maintenance area
ECC800e
Issue 07 (2019-12-20)
Item
AC input
Operating
environment
Monitoring module
indicator
Network interface
indicator
Monitor interface
(network
management system
or Web)
Copyright © Huawei Technologies Co., Ltd.
Operation
N/A
N/A
N/A
N/A
N/A
Expected Result Troubleshooting
the
requirements
of the battery
manufacturer.
After
checking that
the battery
screws meet
the
requirements,
mark the
screws for
later check.
Input voltage:
If the input voltage
100–240 V AC
is abnormal, check
the power grid and
Frequency: 50
input cable
Hz/60 Hz
connection.
Ambient
If the humidity or
temperature:
temperature is
–20° C to
abnormal, check the
+65° C
smart cooling
product status.
Humidity:
5–95% RH
(non-condensi
ng)
The monitoring
If the indicator is
module indicator
off or any abnormal
is steady green or
condition occurs,
blinking green.
see
Troubleshooting the
Monitoring System
to rectify the fault.
The green
Check the network
indicator is steady
cable connection.
on, and the
yellow indicator
is blinking.
Export smart
If an alarm is
cooling product
generated by
logs, alarms,
referring to Alarm
temperature,
References or
humidity, as well
contact Huawei
as the operating
technical support.
status and time of
the water sensor,
door status
sensor,
temperature
4 Maintenance
4.4.2
143