Siemens SINAMICS G130 Operating Instructions Manual page 578

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Technical specifications
12.3 Technical specifications
Article number
Recommended fuses
- Line protection
without semiconductor protection
Rated current
frame size to IEC 60269
- Line and semiconductor protection
Rated current
Frame size to IEC 60269
Minimum short-circuit current
Rated output of a typ. 6-pole standard induction motor based on I
1)
The base-load current I
2)
(see "Overload capability").
The base-load current I
3)
(see "Overload capability").
If the auxiliary supply is to be fed in separately from the load supply, e.g., if the control should be able to continue com-
4)
munication if the line voltage fails.
The minimum current required to reliably trigger 3NE1 protective devices.
5)
578
6SL3310-
A
A
A
5)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
1GH31-5AAx
1GH31-8AAx
3NA3240-6
3NA3244-6
200
250
2
2
3NE1225-2
3NE1227-2
200
250
1
1
1600
2400
or I
at 690 V 3 AC 50 Hz.
L
H
Operating Instructions, 07/2016, A5E00331449A
1GH32-2AAx
3NA3252-6
315
2
3NE1230-2
315
1
3000
Inverter chassis units

Advertisement

Table of Contents
loading

Table of Contents