Device overview
2.6 Type plate
Type plate specifications (from type plate above)
Position
Specification
①
②
Output
③
Temperature range
④
Degree of protection
⑤
Duty class
load class
⑥
Cooling method
⑦
Weight
Date of manufacture
The date of manufacture can be determined as follows:
Table 2- 1
Letter/number
32
Value
Input
3 AC
380 ... 480 V
775 A
3 AC
0 ... 480 V
745 A
0 ... 40 °C
IP00
AF
294 kg
Production year and month
Year of manufacture
C
D
E
F
H
J
K
L
M
Three-phase connection
Rated input voltage
Rated input current
Three-phase connection
Rated output voltage
Rated output current
Ambient temperature range within which the built-in unit can
operate under 100% load
Degree of protection
(for frame sizes FX, GX: IP20 for frames size HX, JX: IP00)
I
I: Duty class I to EN 60146-1-1 = 100% (continuously)
( with the specified current values, the built-in unit can oper-
ate continuously under 100% load)
A: Cooling medium: air
F: Circulation method: forced cooling, drive unit (fan) in the
device
Type plate of built-in unit
Letter/number
2012
2013
2014
2015
2016
2017
2018
2019
2020
Explanation
Month of manufacture
1 ... 9
January to September
O
N
November
D
December
Operating Instructions, 07/2016, A5E00331449A
October
Inverter chassis units