Acceptance test wizard of SINUMERIK Operate
3.3 SINUMERIK 840D sl - system-integrated Safety Functions
3.3.3.3
Switch-off signal path
You can test the switch-off signal paths in the "Switch-off signal path" setting area. Follow the
instructions in the detailed display.
Figure 3-17
You can make the following settings here, for example:
● Enter conditions to initiate the test
● Select acquired alarms that should appear in the report
● Confirm a test result
3.3.3.4
Function relations
User-specific test cases for safety-related functions can be saved in test type "Function
relations". After the test case has started, the user executes the steps required at the system
itself. He observes the response/behavior, and documents the test result that has been
monitored.
Example of a function to be tested
When the machining area door is opened, safety function "Safe operating stop" (SBH) must
be selected for all axes of mode group 1 (BAG 1).
50
Test type/setting range switch-off signal path
SINUMERIK Operate acceptance test
Function Manual, 08/2018, A5E39460574B AC