Configuring/address space
4.1 Operating with "Counting and measurement" technology object
4.1.3

Parameter setting

You specify the properties of the technology module using various parameters. Depending
on the settings, not all parameters are available. When parameters are assigned in the user
program, the parameters are transferred to the module with the "WRREC" instruction and
data record 128 (Page 93).
You set the parameters of the module as follows in this operating mode:
1. Insert the module from the hardware catalog under "Technology modules".
2. Set the device configuration in the hardware configuration.
"Operating with "Counting and measurement" technology object" must be set as the
operating mode.
3. Insert the High_Speed_Counter or SSI_Absolute_Encoder technology object from the
project tree in folder "Technology objects > Add new object > Counting and
measurement".
You can find information on configuring with a technology object in function manual
Counting, Measurement and Position Detection
(http://support.automation.siemens.com/WW/view/en/59709820).
4. Open the configuration of the respective technology object, e.g. using the Configuration
button
5. Set the parameters of the technology object.
6. Download the project to the CPU.
Note
The "Operating with "Counting and measurement" technology object" and "Manual operation
(without technology object)" operating modes apply to one channel in each case. As a result,
you can also use a module with both operating modes.
34
in the respective instruction for the technology object.
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)
Manual, 06/2018, A5E03982218-AB