PIPING INSTALLATION
Condensate Drain Trap
This unit is equipped with a stainless steel condensate pan with a
stainless steel connection. It is important that the drain connection
be fitted with a P trap to ensure proper drainage of condensate while
maintaining internal static pressures and to prevent migration of
sewer gas back into the unit.
A P trap assembly (kit) is supplied with each unit and is to be
assembled and installed as local conditions require and according to
the assembly instructions provided with the P trap. If local and area
codes permit, the condensate may be drained back onto the roof,
but a drip pad should be provided beneath the outlet. If local and
area codes require a permanent drain line, it should be fabricated
and installed in accordance with Best Practices and all codes.
In some climates, it will be necessary to provide freeze protection for
the P trap and drain line. The P trap should be kept filled with water
or glycol solution at all times and it should be protected from freez-
ing to protect the P trap from damage. If severe weather conditions
occur, it may be necessary to fabricate a P trap and drain line of
metal and install a heat tape to prevent freezing.
Condensate Overflow Switch
This unit is equipped with an optional factory-mounted condensate
overflow switch. In the event that a high level of condensate is de-
tected, a dry contact will be powered (24 VAC). This dry contact can
be used for field monitoring of condensate levels. All monitoring and
control shall be provided by others.