Parameters

All parameters
No.
Name/
Value
10 START/STOP/DIR
1001
EXT1
COMMANDS
NOT SEL
DI1
DI1,2
DI 1P,2P
DI1P,2P,3
Description
Defines the sources for external start, stop and
direction control.
Defines the connections and source for start, stop and
direction commands for external control location 1
(EXT1).
Note: Timer stop/start, Counter stop/start and
Sequence programming is not applicable for solar
pump inverter.
No start, stop and direction command source.
Start and stop through digital input DI1.
0 = stop, 1 = start.
Direction is fixed according to parameter
DIRECTION
(setting REQUEST = FORWARD).
Start and stop through digital input DI1.
0 = stop, 1 = start.
Direction is set through digital input DI2. 0 = forward, 1
= reverse. To control the direction, set the parameter
1003 DIRECTION
= REQUEST.
• Pulse start through digital input DI1. 0 -> 1: Start.
Note: To start the inverter, activate the digital input DI2
prior to the pulse fed to DI1.
• Pulse stop through digital input DI2. 1 -> 0: Stop.
The direction of rotation is fixed according to
parameter
1003 DIRECTION
FORWARD).
Note: If you deactivate (no input) the stop input (DI2),
the control panel start and stop keys are disabled.
• Pulse start through digital input DI1. 0 -> 1: Start.
Note: To start the inverter, activate the digital input DI2
prior to the pulse fed to DI1.
• Pulse stop through digital input DI2. 1 -> 0: Stop.
• Direction through digital input DI3.
0 = forward, 1 = reverse.
To control direction, set parameter
= REQUEST.
Note: If you deactivate (no input) the stop input (DI2),
the control panel start and stop keys are disabled.
Actual signals and parameters 41
1003
(setting REQUEST =
1003 DIRECTION
Def/ FbEq
SOLAR
0
1
2
3
4