22 Quick start-up

Installing control cables

Default I/O connections

Max. 500 ohm
1)
AI1 is used as a speed reference if vector mode is selected.
2)
360 degree grounding under a clamp.
Tightening torque = 0.4 N·m / 3.5 lbf·in.
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Not in use by default. 0...10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Not in use by default. 0...10 V
6
GND
Analog input circuit common
7
AO
Output frequency value: 0...20 mA
8
GND
Analog output circuit common
2)
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
-
14 DI3
-
15 DI4
-
16 DI5
-
X1B
17 ROCOM
18 RONC
19 RONO
20 DOSRC
21 DOOUT
22 DOGND
X1C:STO
1
OUT1
STO (Safe torque off) connection
2
OUT2
3
IN1
4
IN2
1)
Relay output 1
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]