Dc Link Fuses; Parallel Connections Of Motor Modules - Siemens SINAMICS G130 Engineering Manual

Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

DC link fuses

DC link fuses are integrated in the power unit of every Motor Module. When a DC coupling (option L37) is installed,
the fuses are integrated in the DC switch.

Parallel connections of Motor Modules

Motor Module
P
at 400 V
M
Frame size
[kW]
Supply voltage 380 V - 480 V 3AC
FX
110
FX
132
GX
160
GX
200
GX
250
HX
315
HX
400
HX
450
JX
560
JX
710
JX
800
P
at 500 V
M
[kW]
Supply voltage 500 V - 600 V 3AC
FX
55
FX
55
FX
75
FX
90
GX
110
GX
132
GX
160
GX
200
HX
250
HX
315
HX
400
JX
500
JX
560
JX
630
JX
710
JX
900
Minimum motor cable length for parallel connection
A cross-connection of the motor terminal lugs between the individual modules is not available. Combined terminal
lugs are available on request with an additional cabinet.
1
These data relate to units with supply voltages of 500 V to 690 V 3AC (MLFB 6SL3720- 1TGxx-xAA0) and 660 V to 690 V 3AC
(MLFB 6SL3720-1 THxx-xAA0).
If two Motor Modules are connected in parallel, imbalances in the current distribution can
occur despite the current compensation control. As a result, a derating factor of 5 %
applies to parallel connections. Parallel connections may only include Motor Modules with
identical voltage rating and identical output power rating.
For the purpose of decoupling, parallel-connected Motor Modules must be configured with
the minimum cable lengths specified below. The specified power ratings are the values for
a single Motor Module.
Motor supply cable
I
Minimum length
rated
[A]
[m]
210
30
260
27
310
20
380
17
490
15
605
13
745
10
840
9
985
8
1260
6
1405
5
1
85
80
100
72
120
65
150
55
175
50
215
40
260
32
330
25
410
20
465
18
575
15
735
13
810
11
910
10
1025
8.5
1270
7
SINAMICS S120 Cabinet Modules
Engineering Information
Motor Module
P
at 690 V
M
Frame size
[kW]
Supply voltage 660 V - 690 V 3AC
FX
75
FX
90
FX
110
FX
132
GX
160
GX
200
GX
250
GX
315
HX
400
HX
450
HX
560
JX
710
JX
800
JX
900
JX
1000
JX
1200
SINAMICS Engineering Manual - May 2008
Motor supply cable
Minimum length
I
[A]
rated
[m]
1
85
100
100
90
120
80
150
70
175
60
215
50
260
40
330
30
410
25
465
25
575
20
735
18
810
15
910
12
1025
10
1270
8
281/396
© Siemens AG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s120 chassisSinamics s150