Maximum connectable motor cable lengths

Booksize units

The Motor Modules generate an AC voltage to supply the connected motor from the DC link voltage. Capacitive
leakage currents are generated in clocked operation and these limit the permissible length of the motor cable.
The following maximum motor cable lengths have to be taken into account:
Line supply
Output power
voltage
Without reactor or filter
380 V – 480 V
1.6 kW - 4.8 kW
3AC
2*1.6 kW – 2*9.7 kW
9.7 kW
16 kW - 107 kW
Permissible motor cable lengths for SINAMICS S120 Booksize units
Where a longer motor cable is required, a higher rating of Motor Module must be selected or the permissible con-
tinuous output current I
continuous
The configuring data for Booksize format Motor Modules are given in the following table:
Length of motor cable (shielded)
Rated output
> 50 m to 100 m
current
3 A / 5 A
9 A
18 A
I
I
contin.
30 A
45 A / 60 A
85 A / 132 A
200 A
Permissible motor cable lengths for over-dimensioned modules
The permissible cable length for an unshielded motor cable is 150 % of the length for a shielded motor cable.
Motor reactors can also be used on motors operating in vector and V/f control modes to allow the use of longer motor
cables. Motor reactors limit the rate of rise and magnitude of the capacitive leakage currents, thereby allowing longer
motor cables to be used. The motor reactor and motor cable capacitance form an oscillating circuit which must not be
excited by the pulse pattern of the output voltage. The resonant frequency of this oscillating circuit must therefore be
significantly higher than the pulse frequency. The longer the motor cable, the higher the cable capacitance and the
lower the resonant frequency. To provide a sufficient safety margin between this resonant frequency and the pulse
frequency, the maximum possible motor cable length is limited, even when several motor reactors are connected in
series.
Rated output
current
3 A – 9 A
2*3 A – 2*18 A
18 A
30 A – 200 A
must be reduced in relation to the rated output current I
> 100 m to 150 m
Use 9 A
Motor Module
Motor Module
Use 18 A
Motor Module
Motor Module
Use 30 A
Motor Module
Motor Module
or
≤ 1.5 * I
max
rated
≤ 0.95 * I
rated
Permissible
I
max
I
contin.
Permissible
I
max
I
contin.
Permissible
I
max
I
contin.
Permissible
I
max
I
contin.
Maximum permissible motor cable length
Con-
Shielded cable
struction
type
Single
Double
Single
Single
100 m
> 150 m to 200 m
Use 9 A
Not permissible
Use 18 A
Not permissible
Use 30 A
Not permissible
≤ 1.35 * I
≤ 1.1 * I
I
rated
max
≤ 0.9 * I
≤ 0.85 * I
I
rated
contin.
≤ 1.75 * I
≤ 1.5 * I
I
rated
max
≤ 0.9 * I
≤ 0.85 * I
I
rated
contin.
≤ 1.35 * I
≤ 1.1 * I
I
rated
max
≤ 0.95 * I
≤ 0.9 * I
I
rated
contin.
≤ 1.25 * I
≤ 1.1 * I
I
rated
max
≤ 0.95 * I
≤ 0.9 * I
I
rated
contin.
SINAMICS Engineering Manual - May 2008
SINAMICS S120
Engineering Information
Unshielded cable
50 m
75 m
50 m
75 m
70 m
100 m
150 m
.
rated
> 200 m
Not permiss ble
Not permiss ble
Not permiss ble
Not permiss ble
rated
rated
Not permiss ble
rated
rated
Not permiss ble
rated
rated
Not permiss ble
rated
rated