Line fault
Fault ride through in accordance with grid codes, occurs automatically via the grid inverter
according to the required parameter settings.
Block diagram
Figure 7-3
Table 7- 8
Number
Grid infeed
System Manual, 04/2015, A5E03347436A
7.5 Commissioning example of an infeed with dynamic grid support for a power grid
Infeed to a power grid
Components for infeed to a power grid
Description
1
Photovoltaic plant
1a
Optional DC contactor
2
Active Line Module
3
Active Interface Module with integrated Voltage Sensing Module VSM10
4
Grid transformer
5
Circuit breaker
6
VSM10 Voltage Sensing Module for measuring the line voltage on the primary side of
the grid transformer
7
Power grid
8
Control Unit
Commissioning
87