Risk of fire due to overheating when the device fan voltage is insufficient
If the terminals are not reconnected to the actual line voltage, this can lead to overheating
with a risk of personal injury due to smoke and fire.
This can also cause the fan fuses to blow due to overload.
• Set the terminals in accordance with the actual line voltage.
Table 8- 9
Note
For devices with connection voltages of 320 V ... 480 V, for operation on a main grid with
voltages <380 V, direct supply from the main grid is not possible. In this case, a separate
power supply for the device fan with 1 AC 400 V must be provided; the current drawn by the
fan can be taken from the technical data. The taps for the fan transformer must be selected
for 400 V.
Table 8- 10
Grid infeed
System Manual, 04/2015, A5E03347436A
8.4 Air-cooled Active Line Modules for the grid infeed, chassis format
WARNING
Line voltage assignment for the setting at the fan transformer (320 ... 480 V 3 AC)
Grid voltage
< 380 V
380 V ± 10%
400 V ± 10%
440 V ± 10%
480 V ± 10%
Line voltage assignment for the setting at the fan transformer (500 ... 690 V 3 AC)
Grid voltage
500 V ± 10%
525 V ± 10%
575 V ± 10%
600 V ± 10%
660 V ± 10%
690 V ± 10%
Tap at the fan transformer (-T10)
Separate power supply required
380 V
400 V
440 V
480 V
Tap at the fan transformer (-T10)
500 V
525 V
575 V
600 V
660 V
690 V