Siemens SINAMICS S120 System Manual page 113

Grid infeed
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

● Corresponding to function diagram FP7990, different measuring tasks are uniquely
assigned to the various VSM10 devices; it is not permissible to change this assignment.
For an assignment of the various VSM10, see the diagram in the subsequent chapter, the
assignment of the VSM10 to the numbers in the diagram are as follows:
VSM_1 =
– VSM_1 is, according to a possible parallel connection of power units and grid filters,
– VSM_2 is defined with p0151[0]; the measured values are displayed in r5461[0] and
– VSM_3 is defined with p0151[1]; the measured values are displayed in r5461[1] and
Overview of important parameters
● p5401 BI: Line droop control activation
● p5483 BI: Line circuit breaker enable
● p5486[0] Transformer rated voltage primary - infeed transformer
● p5487[0, 1] CI: Transf primary voltage signal source - infeed transformer
● p5580 Island grid black start mode
● p5581[0...4] Island grid times - black start
● p5586[0] Black start voltage limit
Function block diagrams
● 7988 Island grid black start sequence control
Grid infeed
System Manual, 04/2015, A5E03347436A
, VSM_2 =
assigned to p0141 (measured values r3661, r3662).
r5462[0].
r5462[1].
7.7 Commissioning the grid droop control
, VSM_3 =
.
Commissioning
113