9

Alarm Handling

For more alarm handling, see the UPS2000-G-(1 kVA-3 kVA) User Manual.
Ala
Ala
Alarm
rm
rm
Name
ID
Cau
se
ID
10
1
Bypass
voltage
abnorm
al
2
Bypass
frequen
cy
abnorm
al
22
1
Battery
disconn
ected
Alarm
Alarm
Sever
Clear
ity
Mode
Minor
This
alarm is
automatic
ally
cleared.
Minor
This
alarm is
automatic
ally
cleared.
Minor
This
alarm is
automatic
ally
cleared.
Trigger
Impact on
Condition
the System
The
The UPS
bypass
remains in the
voltage is
current state.
outside the
If the UPS
scope.
works in
bypass mode,
it transfers to
standby mode
and has no
output.
The
The UPS
bypass
remains in the
frequency
current state.
is outside
If the UPS
the bypass
works in
frequency
bypass mode,
range.
it transfers to
standby mode
and has no
output.
Batteries
The power
are not
supply from
connected,
the UPS is not
connected
affected.
improperly,
or
damaged.
11
Repair Proposal
Possible causes:
The bypass input
voltage is
abnormal.
Measures: Check
whether the bypass
input voltage
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
Possible causes:
The bypass input
frequency is
abnormal.
Measures: Check
whether the bypass
input frequency
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
Possible cause:
No batteries are
connected.
Measure:
Connect
batteries.
Possible cause:
The batteries
are in poor
contact.
Measure: Check
the battery
cable
connection. If
battery cables
are loose,
connect them
securely.