Siemens Simatic Ident Function Manual page 125

Rfid systems ident profile and ident blocks, standard function for ident systems
Hide thumbs Also See for Simatic Ident:
Table of Contents

Advertisement

Error mes-
Description
sage
(hex)
0xE2FE8600
The carrier signal is not activated.
0xE2FE8700
There is more than one transponder in the transmission window.
0xE2FE8800
General radio protocol error
0xE4FE0100
Short circuit or overload of the 24 V outputs
The reader is using too much current.
The reader cable is causing a short-circuit.
Possible consequences:
The affected output is turned off
All outputs are turned off when total overload occurs
A reset can only be performed by turning the 24 V voltage off and on again
and then starting "Reset_Reader"
0xE4FE0300
Error in the connection to the reader; the reader is not answering.
The cable between the communications module and reader is wired incorrectly or there is a cable
break
The 24 V supply voltage is not connected or is not on or has failed briefly
Automatic cutout on the communications module has responded
Hardware defect
Another reader is in the vicinity and is active
Execute "INIT"/"WRITE-CONFIG" after correcting the error
The antenna of the reader is turned off. A tag command to the communications module was started in
this status.
Turn on the antenna with the command "Antenna on/off."
The antenna is turned on (off) and has received an additional turn-on (turn-off) command
The mode in the "SET_ANT" command is unknown
The antenna on the reader is turned off or the antenna cable is defective
0xE4FE0400
The buffer on the communications module or reader is not adequate to store the command temporarily.
0xE4FE0500
The buffer on the communications module or reader is not adequate to store the data temporarily.
0xE4FE0600
The command is not permitted in this status or is not supported.
RF61xR/RF68xR: Command repetition is only possible in Presence mode.
0xE4FE0700
Startup message from reader/communications module. The reader or communications module was turned
off and has not yet received a "Reset_Reader" ("WRITE_CONFIG") command.
Execute "INIT"
The same physical address in the "IID_HW_CONNECT" parameter is being used more than once.
Check your "IID_HW_CONNECT" parameter assignments.
Check connection to the reader
The transmission speed was switched over but power has not yet been cycled
0xE4FE8100
Reserved
0xE4FE8A00
General error
0xE4FE8B00
No or bad configuration data was transferred.
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
4.3 Errors from the communications module/reader
Error messages
125