Technical Specifications
Unless explicitly specified otherwise, the following technical specifications are valid for
components of the SINAMICS S120 booksize drive system.
Electrical specifications
Line connection voltage
Line frequency
Electronics power supply
Conducted radio interference
Standard
With line filter
Overvoltage category
*
If a motor holding brake is used, restricted voltage tolerances may have to be taken into account.
Modules
Line Modules in booksize format
Rated supply voltage
Active Line Modules in booksize format
Rated pulse frequency
Motor Modules in booksize format
DC link connection voltage
Rated pulse frequency
Ambient conditions
The Safety-Integrated safety function:
The components must be protected against conducted contamination (e.g. by installing them in a cabinet with degree of
protection IP54).
Provided that conducted interference can be prevented at the installation site, the degree of protection for the cabinet can
be decreased accordingly.
Degree of protection
Protection class
Permissible ambient and coolant temperature (air) during
operation for line-side components, Line Modules and Motor
Modules
Permissible ambient and coolant temperature (air) during
operation for DC link components
1-10
3 AC 380 V to 480 V ±10 %
(-15 % < 1 min)
47 – 63 Hz
24 V DC, -15/+20 %*
No conducted radio interference
Class A1 to EN 55011
Class III to EN 60 664-1
3AC 380 V
8 kHz
510 V DC to 750 V DC
4 kHz
IP20 to EN 60 529
Class I (with protective conductor system) and
Class III (PELV) to EN 61 800-5-1
0°C to 40 °C without derating,
>40°C to +55 °C (see derating characteristics)
0 °C to +55 °C
Equipment Manuel for Booksize Power Modules