Line Modules Booksize
3.6 Smart Line Modules (5 kW and 10 kW) with external air cooling
3.6.3.5
X22 terminals: smart line module
Table 3-39
Terminal block X22
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Connection Methods)
3.6.3.6
X24 24 V terminal adapter
Table 3-40
Terminal block X24
Terminal
+
M
The 24 V terminal adapter is supplied as standard
Max. connectable cross-section: 6 mm
Type: Screw terminal 5 (see Connection Methods)
3-82
Name
24 V power supply
DI: Disable Regeneration
DI: Reset
Ground
2
Name
24 V power supply
Ground
2
Technical specifications
Electronics power supply for controlling digital inputs
X22.2 and 3.
Deactivate feedback
No power is supplied back to the network from the DC
link. The regenerative energy of the motors may have
to be reduced using a combination of the Braking
Module and braking resistor.
Reset faults (positive edge)
Electronic ground
Technical specifications
24 V DC supply voltage
Electronic ground
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2