Cabinet Configuration and EMC Booksize
7.4 Arrangement of components and devices
7.4
Arrangement of components and devices
7.4
7.4.1
General
The arrangement of the components and equipment takes account of
• Space requirements
• Cable routing
• Bending radius of connection cables
• Heat dissipation
• EMC
Components are usually located centrally in a cabinet.
7.4.2
Drive line-up
Due to the current carrying capacity of the DC link busbars and their function, the
components must be arranged according to the following rule. From left to right:
• Line Module
• Motor Modules in order of power from the highest power to the lowest power
• DC link components (e.g. Braking Module, Control Supply Module, Capacitor Module)
7-14
For MOTION-CONNECT cables, see catalog D21.1 or D21.2.
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2