Rear access connection

Withdrawable pattern

Type S - 3 pole - Frame size 1, In=400A to 1600A
Centre line of operating panel
Type S - 4 pole - Frame size 1, In=400A to 1600A
Centre line of operating panel
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.
Centre line of
operating panel
35 Test
50 Disconnected
275 Fully withdrawn
Copperwork must be supported within 200 mm of breaker
connections-busbars or cables. All connections to be tightened to 50Nm.
to door
Minimum clearance
to cassette side
Connected
to door
Connected
M-PACT Plus
Ventilation
Minimum clearance
to cassette side
Ventilation
A
B
C
X
C.7