8

ACH580-01 Installation

Installation
Study these installation instructions carefully before proceeding. Failure to observe
the warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read
1. Check free space requirements
The drive must be installed on the wall. There are two alternative ways to install it.
Note: Do not install upside down.

Vertically alone

ACH580-01 Installation
a
c
b
ACH580 Installation, Operation and Maintenance Manual
Safety instructions
Vertical installation - Free space
Frame
1)
Above (a)
size
mm
in
R1
200
7.87
R2
200
7.87
R3
200
7.87
R4
53
2.09
R5
100
3.94
R6
155
6.10
R7
155
6.10
R8
155
6.10
R9
200
7.87
1) Free space above is measured from the frame, not from the hood used
in UL (NEMA) Type 12 frames.
Note: The height of the hood for frames R4 and R9 exceeds the
requirement of free space above for these frames..
Frame size
Hood height (in)
Hood height (mm)
2)
Free space below is measured from the frame, not from the cable box
used in frames R1...R2 and R5...R9.
3)
Free space between the drive and other objects, e.g. wall.
on page 2.
2)
Below (b)
Beside (c)
mm
in
mm
150
5.91
150
5.91
150
5.91
150
5.91
200
7.87
150
5.91
200
7.87
150
5.91
200
7.87
150
5.91
300
11.81
150
5.91
300
11.81
150
5.91
300
11.81
150
5.91
300
11.81
150
5.91
3AXD00000586715.xls K
R4
R9
2.83
9.06
72
230
3)