ACH580 Installation, Operation and Maintenance Manual

Warning listing

The following table lists the warnings by code number and describes each.
Warning
Code
4001
4002
4003
4004
4005
4006
4007
Warning Name In
Panel
INP PHASE A
Warning will occur in
LOSS
drive mode. In bypass,
warning will occur if
bypass contactor has
not closed. Unit will trip
on Fault 3010 if the
bypass contactor is
closed
INP PHASE B
Warning will occur in
LOSS
drive mode. In bypass,
warning will occur if
bypass contactor has
not closed. Unit will trip
on Fault 3011 if the
bypass contactor is
closed
INP PHASE C
Warning will occur in
LOSS
drive mode. In bypass,
warning will occur if
bypass contactor has
not closed. Unit will trip
on Fault 3012 if the
bypass contactor is
closed
AUTO TRANSFER
Message is displayed
when the drive faults
and the bypass
switches to bypass
mode as configured in
Parameter 1608
EXT COMM ERR
Time between fieldbus
messages has
exceeded timeout
interval set with
parameter 3005
Selected by PAR
Warning will occur
1620:
when start order is
given and the
PERMISSIVE
"Permissive" is not
DAMPER END
present
SWITCH
VALVE OPENING
PRE-LUBE CYCLE
PCB TEMP
RBCU unit reached
181 degrees
Fahrenheit, 83 degrees
Celsius
Warning
Possible Cause
Loose J8 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Loose J8 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Loose J8 connector
Loose wiring on
Contactor assembly.
Blown upstream fuse
Drive fault
Incorrect
Communication
settings in Group 51
& 53.
Poor Connections
Noise on
Communication Line
Permissive condition
is not satisfied.
Bad 24v supply
Bad digital input
Cabinet cooling has
failed
Ambient conditions
too high
Bad RBCU unit
129
Corrective Action
Check J8 connector
Check yellow wire on
input block
Check incoming
voltage, phase to
ground
Check J8 connector
Check black wire on
input block
Check incoming
voltage, phase to
ground
Check J8 connector
Check red wire on input
block
Check incoming
voltage, phase to
ground
Check drive
Check Group 51 & 58
Tighten Connections
Check Communication
Cable Grounding
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
for status of digital input
Stop drive and let cool
down and restart
Add additional cooling
Replace RBCU