7SR210 & 7SR220 Applications Guide
5.5
Inrush Detector (81HBL2)
This element detects the presence of high levels of 2nd Harmonic current which is indicative of transformer Inrush
current at switch-on. These currents may be above the operate level of the overcurrent elements for a short
duration and it is important that the relay does not issue an incorrect trip command for this transient network
condition.
If a magnetic inrush condition is detected operation of the overcurrent elements can be blocked.
Calculation of the magnetising inrush current level is complex. However a ratio of 20% 2
Fundamental current will meet most applications without compromising the integrity of the Overcurrent protection.
There are 3 methods of detection and blocking during the passage of magnetising inrush current.
Phase
Blocking only occurs in those phases where Inrush is detected.
Large, Single Phase Transformers – Auto-transformers.
Cross
All 3-phases are blocked if Inrush is detected in any phase.
Traditional application for most Transformers but can give delayed operation for Switch-
on to Earth Fault conditions.
Sum
Composite 2nd Harmonic content derived for all 3-phases and then compared to
Fundamental current for each individual phase.
Provides good compromise between Inrush stability and fast fault detection.
5.6
Broken Conductor / Load Imbalance (46BC)
This feature is used to detect an open circuit condition when a conductor breaks or a mal-operation occurs in
phase segregated switchgear.
There will be little or no fault current and so overcurrent elements will not detect the condition. However the
condition can be detected because there will be a high content of NPS (unbalance) current present.
An NPS / PPS ratio > 50% will result from a Broken Conductor condition.
Operation is subject to a time delay to prevent operation for transitory effects.
5.7
Circuit-Breaker Maintenance
The Relay provides CB Total Trip Count, CB Delta Trip Count, CB Count to AR Block and CB Frequent Operation
2
Counters along with an I
Breaker. Alarm can be provided once set levels have been exceeded.
Typically estimates obtained from previous circuit-breaker maintenance schedules or manufacturers data sheets
are used for setting these alarm levels. The relay instrumentation provides the current values of these counters.
5.8
Overfluxing Detector (81HBL5)
An increase in transformer or decrease in system frequency may result in the transformer becoming over-excited.
The 81HBL5 element can be used to prevent protection operation e.g. prevent differential protection operation
during acceptable over-excitation conditions.
Page 42 of 48
Table 5-5
t CB Wear Counter to estimate the amount of wear and tear experienced by a Circuit-
Magnetic Inrush Bias
©2018 Siemens Protection Devices Limited
nd
Harmonic to