Circuit Breaker; Quick Logic - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

3.11.5.

Circuit Breaker

Description
Gn Close CB Pulse
Specifies the duration of the circuit breaker close pulse
Gn Reclaim Timer
The period of time after a CB has closed and remained closed
before the reclosure is deemed to be successful and the AR is
re-initialised. If the CB remains open at the end of the reclaim
time then the AR goes to lockout.
Gn Minimum LO Delay
Gn Reset LO By Timer
Gn CB Control Trip Time
Gn Trip Time Alarm
An alarm is issued when the Trip time is exceeded
Gn Trip Time Adjust
Adjustment to take into account any binary input delays for
Trip Time Alarm
Gn CB Travel Alarm
Selects the maximum time that the CB should take to either
Open or Close before a failure is recorded.
Gn Open CB Pulse
Selects the maximum time of the Open CB pulse. If the CB is
not closed when this timer expires then an alarm will be raised
to signify failure to close.
Gn CB DBI Delay
Selects the Delay before relay goes to Lockout following a
simultaneous Open and Close condition indication.
3.11.6.

QUICK LOGIC

Description
Quick Logic
Enable or Disable all logic equations
E1 Equation
Enable or Disable logic equation E1
E1
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation.
= AND operation^ = EXCLUSIVE OR operationE(followed by a
digit) = Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed
by a digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when
function key is pressed
(requires E1 to drive L11 in output
matrix)E1 = F3^L11
E1 Pick-up Delay
Time before equation output operates, after equation satisfied
E1 Drop-off Delay
Time before equation output resets, after equation nolonger
satisfied
Unrestricted ©2018 Siemens Protection Devices Limited
Range
0, 0.1 ... 19.9, 20
0, 1 ... 599, 600
0, 1 ... 599, 600
Disabled, Enabled
Disabled, Enabled
0, 0.01 ... 1.99, 2
0, 0.005 ... 1.995, 2
0.01, 0.02 ... 1.99, 2
0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8,
0.9, 1, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6,
1.7, 1.8, 1.9, 2
0, 0.01, ... 1.1, 1.11 ... 2
Range
Disabled, Enabled
Disabled, Enabled
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
7SR220 Settings Guide
Default
2 s
2 s
2 s
Enabled
Enabled
0.2 s
0.015 s
1 s
1 s
0 s
Default
Disabled
Disabled
0 s
0 s
Page 49 of 107