Operate And Reset Level; Time Delayed Derived Earth Fault; Reference - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.16 51N Time Delayed Derived Earth Fault

2.16.1 Reference

Parameter
Is
Setting
char
Characteristic setting
Tm
Time Multiplier setting
t
Delay setting
d
t
Reset setting
res

2.16.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Variation
Unrestricted © 2013 Siemens Protection Devices Limited
- 10 °C to + 55 °C
+ 2 Hz £ 5 %
f
- 3 Hz to f
nom
nom
7SR21 & 7SR22 Performance Specification
Value
0.05, 0.06... 2.5 xIn
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
0.025, 0.05... 1.6
0, 0.01... 20 s
ANSI DECAYING, 0, 1... 60 s
Value
105 % Is, ± 4 % or ± 1% In
³ 95 % I
op
± 1 %
£ 5 %
Page 43 of 68

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Argus 7sr22

Table of Contents