Standalone Application - Siemens FDA241 Technical Manual

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Commissioning
7

Standalone application

7.2
82
Building Technologies
Fire Safety
Standalone application
With the standalone option, the aspirating smoke detector is not connected to a fire
control panel and is not configured using the configuration software for the
FS20/FS720.
 The aspirating smoke detector is correctly installed.
 The aspirating smoke detector is correctly connected to an external power unit.
 The aspirating smoke detector is correctly connected to a pipe system.
 Communication transponder FDCC221S is not installed.
1. Switch the power supply on.
2. Carry out an LED and buzzer test. See 'LED and buzzer test [➙ 89]'.
3. Carry out the required normalization [➙ 90].
 The aspirating smoke detector works with the basic settings.
 If a fault occurs or the housing cover is open, the fault indicator
 If the
button is pressed when the housing cover is open, the buzzer
switches off and the relay outputs are deactivated. The 4...20 mA analog
output remains on fault.
 The three green LEDs light up during normal operation.
Normal operation
Normal operation, green LEDs light up
Use the 'FXS2051 ASD Configuration Tool' software to change the basic settings.
See also
 Mounting [➙ 58]
 Communication with the aspirating smoke detector [➙ 94]
 Faults [➙ 101]
flashes.
A6V10334410_h_en_--
2015-09-29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fda221

Table of Contents