GE VersaPoint IC220PBI002 User Manual page 198

Profibus-dp niu
Table of Contents

Advertisement

D
EndModule
Module="IC220PWR013*SEG TERM F-D 24VDC"
0x42,0x00,0xBE,0xC2
EndModule
Module="IC220PWR014*SEG TERM ELF 24VDC"
0x42,0x00,0xBE,0xC2
EndModule
;*********************************************
;********* device diagnostics *****************
;******************************************
*********************************************
;********* PROFIBUS standard diagnostics *****
; Byte 0 station state 1
; Byte 1 station state 2
; Byte 2 station state 3
; Byte 3 PROFIBUS master address
; Byte 4 00H (manufacturers ID high Byte)
; Byte 5 00H (manufacturers ID low Byte)
;********************************************
;********************************************
;********* device specific diagnostics *****
;********************************************
; Byte 6 0AH (Header Byte, number of following byte)
; Byte 7 00H (type of diagnostics)
; Byte 8 firmware revision, ASCII coded
; Byte 9 error type
; Byte 10 error number
; meaning of error type-error number:
; 1: parameterization error PROFIBUS
; 2: configuration error PROFIBUS
; 2-1: less modules configured than connected
; 2-2: more modules configured than connected
; 2-3: 1st byte of special signature format is incorrect
; 2-4: for last module not enough byte of special signature format
configured
; 2-5: sum of configured process data > 184 byte
; 2-6: different ID codes for configuration and module
; 2-7: different length codes for configuration and module
; 2-8: number of manufacturer specific data is incorrect
; 2-9: not enough output bytes configured
; 2-10: not enough input bytes configured
; 2-11: configuration of PROFIBUS needs more than 244 bytes
; 3: configuration error local bus station
; 3-1: module not allowed
; 3-2: module length code is zero
; 3-3: module length code > 32 byte
; 3-4: module not allowed
D-24
VersaPoint™ I/O System Profibus-DP NIU User's Manual August 2005
; 3-5: sum of local bus process data too large
; 3-6: more than 64 modules connected
; 3-7: sum of PROFIBUS process data > 184 Byte
; 4: local bus error
; 4-1: local bus error (Data In)
; 4-2: local bus error (Data Out)
; 4-3: error can not be localized
; 4-4: localbus module not ready
; 4-5: new local bus module has an incorrect length- or ID-
code
; 4-6: additional local bus module connected
; 5: module error
; 5-1: peripheral fault
; Byte 11 local bus module before fault (or module with
peripheral fault)
; Byte 12 local bus module after fault (or module with
peripheral fault)
; Byte 13 local bus module ID code
; Byte 14 local bus module length code
; Byte 15 reserved
;************************************************
;******** error type *************************
Unit_Diag_Area = 16-23
Value(1) = "#1-parameter error PROFIBUS"
Value(2) = "#2-PROFIBUS configuration error"
Value(3) = "#3-local bus configuration error"
Value(4) = "#4-local bus error"
Value(5) = "#5-module error"
Unit_Diag_Area_End
;******** error number ***************************
Unit_Diag_Area = 24-31
Value(1) = "Error number: #1"
Value(2) = "Error number: #2"
Value(3) = "Error number: #3"
Value(4) = "Error number: #4"
Value(5) = "Error number: #5"
Value(6) = "Error number: #6"
Value(7) = "Error number: #7"
Value(8) = "Error number: #8"
Value(9) = "Error number: #9"
Value(10) = "Error number: #10"
Value(11) = "Error number: #11"
Unit_Diag_Area_End
;******** error location start *******************
GFK-1911B