F424
Load Sharing Gain Input
Program
Torque Setting Parameters
This parameter Enables/Disables the Load Sharing Gain input function and is
enabled by selecting a Load Sharing Gain input signal source.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
LED Keypad Option
Binary/BCD Input
Common Serial (TTL)
RS232/485
Communication Card
Forward Speed Limit Input
Program
Torque Setting Parameters
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the terminal selected here. If Setting is
selected, the value set at
F426
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting
Forward Speed Limit Level
Program
Torque Setting Parameters
This parameter provides a value to be used as the Forward Speed Limit setting
if Setting is selected at F425.
126
Torque Control
Torque Speed Limiting
is used as the Forward Speed Limit input.
Torque Control
Direct Access Number — F424
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F426
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
H7 ASD Operation Manual
F426