Rxgoose Analogs; Wattmetric Ground Fault; Transducer Inputs/Outputs - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
Base unit
SYNCHROCHECK
(Max Delta Volts)
Z
BASE

6.4.7 RxGOOSE analogs

ACTUAL VALUES  METERING  RxGOOSE Analogs
 RxGOOSE
 Analogs
The D30 is provided with optional GOOSE communications capability. This feature is specified as a software
option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.

6.4.8 Wattmetric ground fault

ACTUAL VALUES  METERING  WATTMETRIC GROUND FAULT 1(2)
 WATTMETRIC
 GROUND FAULT 1
This menu displays the wattmetric zero-sequence directional element operating power values.

6.4.9 Transducer inputs/outputs

ACTUAL VALUES  METERING  TRANSDUCER I/O DCMA INPUTS  DCMA INPUT xx
 DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES  METERING  TRANSDUCER I/O RTD INPUTS  RTD INPUT xx
 RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Description
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
Z
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
BASE
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as the
distance source, use the PhaseCTSecondary value from the CT with the highest primary nominal
current.
Distance source is specified in setting under SETTINGS  GROUPED ELEMENTS  SETTING
GROUP 1(6)  DISTANCE.
PhaseVTSecondary and PhaseCTSecondary are specified in setting under SETTINGS  SYSTEM
SETUP  AC INPUTS.
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
WATT GND FLT 1:
0.000 W
DCMA INPUT xx
0.000 mA
RTD INPUT xx
-50 °C
METERING
6
6-21