GE D30 Instruction Manual page 330

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

PRODUCT SETUP
PUSHBUTTON 1 FUNCTION
PUSHBTN 1 DROP-OUT TIME
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the
PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST
LED TEST FUNCTION
LED TEST CONTROL
The test is initiated when the user-programmable pushbutton 1 is pressed. Keep the pushbutton pressed for as long as the
LEDs are being visually inspected. When finished, release the pushbutton. The relay then automatically starts stage 2. At
this point, test can be cancelled by pressing the pushbutton.
Application example 2
Assume one needs to check if any LEDs are "burned" as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. When
finished, release the pushbutton so that the relay then automatically starts stage 2. When stage 2 is completed, stage 3
starts automatically. The test can be cancelled at any time by pressing the pushbutton.
5.3.11.4 Trip and alarm LEDs
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  TRIP & ALARMS LEDS
 TRIP & ALARM LEDS
5
The trip and alarm LEDs are in the first LED column (enhanced and graphical front panels) and on LED panel 1 (standard
front panel). Each LED can be programmed to turn on when the selected FlexLogic operand is in the logic 1 state.
5.3.11.5 User-programmable LED 1(48)
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS  USER-PROGRAMMABLE LED 1(48)
 USER-PROGRAMMABLE
 LED 1
For the enhanced and standard front panels, there are 48 amber LEDs across the relay LED panels. Each of these
indicators can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state.
For the standard front panel, the LEDs are located as follows:
LED Panel 2 — User-programmable LEDs 1 through 24
LED Panel 3 — User programmable LEDs 25 through 48
For the enhanced front panel, the LEDs are located as follows:
LED column 2 — User-programmable LEDs 1 through 12
LED column 3 — User-programmable LEDs 13 through 24
LED column 4 — User-programmable LEDs 25 through 36
LED column 5 — User-programmable LEDs 37 through 48
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination tracks the state of the selected LED operand. If the
"Latched," the LED, once lit, remains so until reset by the front panel
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
5-120
: "Self-reset"
: "0.10 s"
: "Enabled"
:
"PUSHBUTTON 1
ON"
TRIP LED INPUT:
Off
ALARM LED INPUT:
Off
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
menu:
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-Reset, Latched
button, from a remote device via a
RESET
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
SETTINGS 
setting is "Self-
LED 1 TYPE
setting is
LED 1 TYPE