CHAPTER 5: SETTINGS
Unit
FAULT LOCATION
FREQUENCY
FREQUENCY RATE OF CHANGE
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
Z
BASE
— This setting defines the pickup–dropout relation of the element by specifying the width of the
FLEXELEMENT 1 HYSTERESIS
hysteresis loop as a percentage of the pickup value as shown in the FlexElement Direction, Pickup, and Hysteresis diagram.
— Specifies the time unit for the setting
FLEXELEMENT 1 dt UNIT
is set to "Delta."
FLEXELEMENT 1 COMP MODE
— Specifies duration of the time interval for the rate of change mode of operation. This setting is
FLEXELEMENT 1 dt
applicable only if
FLEXELEMENT 1 COMP MODE
— Specifies the pickup delay of the element.
FLEXELEMENT 1 PKP DELAY
— Specifies the reset delay of the element.
FLEXELEMENT 1 RST DELAY

5.6.7 Non-volatile latches

SETTINGS  FLEXLOGIC  NON-VOLATILE LATCHES  LATCH 1(16)
 LATCH 1
The non-volatile latches provide a permanent logical flag that is stored safely and do not reset upon restart after the relay
is powered down. Typical applications include sustaining operator commands or permanently blocking relay functions,
such as Autorecloser, until a deliberate interface action resets the latch.
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Description
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
df/dt
= 1 Hz/s
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
Z
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
BASE
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as the
distance source, use the PhaseCTSecondary value from the CT with the highest primary nominal
current.
Distance source is specified in setting under SETTINGS  GROUPED ELEMENTS  SETTING
GROUP 1(6)  DISTANCE.
PhaseVTSecondary and PhaseCTSecondary are specified in setting under SETTINGS  SYSTEM
SETUP  AC INPUTS.
FLEXELEMENT 1 dt
is set to "Delta."
LATCH 1
FUNCTION: Disabled
LATCH 1 ID:
NV Latch 1
LATCH 1 TYPE:
Reset Dominant
LATCH 1 SET:
Off
LATCH 1 RESET:
Off
LATCH 1
TARGET: Self-reset
LATCH 1
EVENTS: Disabled
× I
for the +IN and –IN inputs
BASE
. This setting is applicable only if
Range: Disabled, Enabled
Range: up to 20 alphanumeric characters
Range: Reset Dominant, Set Dominant
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
FLEXLOGIC
5
5-187