User level 3A

After the door has been opened with the fire brigade key (LED "Door
open" is lit), the service / maintenance personnel have access to
level 2A and after log on as "Service personnel" (level 3A), access to
all menus, i.e. like level 2C and also to the following menus:
Same menus as in access level 2C plus the following:
H5 Service
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for COM-loop
A7 Activate address setting mode for DU
A8 Show information about site specific data
H8 Maintenance
S1 Disconnect / Re-connect COM-loop
S2 Disconnect / Re-connect zone line input
S3 Disconnect / Re-connect addressable zone interface input
S4 Acknowledge SERVICE signal
S5 Restore weekly average to default
S6 Test of alarm devices
S7 Safe shut down of control unit
S8 Activate zone/address in alarm mode
S9 Activate output
S10 Reset activated output
H10 Change password (In this case for "Service personnel".)

Access level 3B

Used by Service / maintenance / commissioning engineers when a PC
(i.e. EBLWin) is to be connected to EBL128 for backup (upload),
download of site specific data (SSD) and/or download of software.
An EBLWin key in the PC is required.

Access level 4

Used by manufacturer or by personnel authorised by the manufacturer
for re-initialisation (reset) of the alarm counter, change software
27