In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up and the alarm point will be automatically reset after about ten
seconds. The alarm will also momentarily be shown in the EBL128 display.
A sensor in test mode will not be able to activate fault.
"↓"
or
"2"
"A"
"Return"
"Return"
Rev: -
Set zone in test mode
End zone in test mode
End test mode zone: 01
--- List is empty ---
End zone in test mode
Perform ZONE TEST
NOTE!
a) If an alarm point (e.g. a manual call point) is in alarm state when
the test mode is ended, there will be a fire alarm activated.
b) When the "Fire door closing" function is used, the fire door(s) will
be closed when the zone involved is set in test mode.
EBL128 Operating Instructions V2.0.x
ACCEPT? D1
ACCEPT? D2
ACCEPT?
ACCEPT? D2
ACCEPT? H7
125
To end the test mode the
menu D1 has to be open.
Press "↓" or "2" to open
menu D2.
(Press "↑" or "1" for menu
D1.)
This is a list in which you
L
can scroll between all the
zones in test mode. Select
or type the zone number
and press "A".
When no more zones are in
test mode
--- List is empty ---
will be shown and the LED
"Test mode" (L9) is turned
OFF.
Press "Return" to D2.
Press "Return" to H7.