Panasonic EBL128 Operating Instructions Manual page 24

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
The priority order is shown in the following table:
Priority
Event
1
Fire alarms (see below)
2
Quiet alarm
3
Co-incidence alarm
4
Delayed alarm
5
Pre-warning
6
Test mode alarm
21
7
AAF alarm
8
Evacuate information
9
New Zealand convention only:
Routing equipment left isolated
10
Fault (not acknowledged)
11
Disablement
12
Zones in "Test mode"
13
Interlocking input / output active
14
Information in normal operation in quiescent state
NOTE! Fire alarms are:
Fire alarm
Heavy smoke/heat alarm
Alert Annunciation (AA) alarm
Key cabinet alarm
Acknowledged alarm (New Zealand only)
Isolated alarm (New Zealand only)
The different type of events and the menu system are described in
other parts of this document. Regarding "priority 14", see page 21.
NOTE!
When "More..." is shown, it is possible to scroll between the items
with "↓" and "↑".
21
The AAF function is used in conjunction with an AAF Control, which is
available on the Australian market only.
22
Only valid for Belgian, British Standard, Hungarian, Spanish and
Ukrainian conventions.
22
EBL128 Operating Instructions V2.0.x
22