EMC measures
The PE conductor connection is also used to conduct interference currents
away from:
S
S
S
To ensure that these interference suppression measures are effective, there
must be a low-resistance connection between the shielding plate and ground
potential.
The low-resistance bonding conductor should be a stranded cable with a cross-
section of at least 10 mm
DMP compact
A maximum of 8 DMP compact modules can be connected per NCU terminal
modules
block.
Module type
DMP compact module 16 I
DMP compact module 16 O
DMP compact module 8 O
DMP compact module 1I analog
DMP compact module 1I NC analog IN
DMP compact module 1O analog
Equipment in max. 2 terminal blocks of a control:
Important
!
A maximum of 4 analog outputs and 4 analog inputs can be plugged in at the
same time for each NCU terminal block.
Caution
!
After the load supply voltage for the DMP compact modules has been switched
off during operation, the outputs do not reliably reestablish through-connection
when the load supply voltage is switched on again. If switch-off during
operation cannot be avoided, the DMP outputs have to be reset via the PLC
program when the load supply voltage is switched off. The outputs are set
again after the voltage has been switched on again.
Copyright © Siemens AG 2006
SINUMERIK 810D Equipment Manual Configuration CCU (PHC) – 03/2006 Edition
the shields of the DMP casing,
the DMP compact plug-in modules,
the 24 V logic power supply.
2
and a length of less than < 30 cm, if possible.
Peripherals
Digital inputs
Digital outputs
Analog inputs
Analog outputs
7 NCU Terminal Block
Max.
Variation
number
2
Digital inputs
2
Digital outputs 0,5 A
4
Digital outputs 2.0 A
8
Analog input 13 bits
Rapid analog input 75 ms, 12 bits
4
4
Analog output 14 bits
Number
32
32
8
8
7-93