Siemens SIWAREX FTA Device Manual page 146

Weighing electronics for automatic scale
Table of Contents

Advertisement

Commands
Code
Command explanation
Delete statistic data
116
The statistic data is deleted except for totalising
memories
117
Output totalizing memory 1
The content of the totalizing memory 1 is output
instead of the calibratable weight value. In AWI
totalizing mode, the totalizing memory 1 will remain
as it is; in other operating modes it will switch back
to the calibratable weight after 5s. Command no.
125 also switches the calibratable weight back on.
118
Empty Off
The empty that was started with command 109 is
ended immediately.
121
Start weighing with/without tare/zero setting
Single start with/without performing a
tare/inspection. The counter for tare and inspection
runs in the background (as in continuous
operation) and decides whether taring or an
inspection should be performed in certain cases.
122
Execute taring/zero setting
Taring/zero setting should be executed with the
next start. After execution, the taring-cycle counter
is reset.
Check follows
123
The inspection should follow. After the execution,
the counter is reset but is only restarted after being
regulated to the optimal regulation.
124
Residual emptying
Continuous operation is stopped and residue is
emptied; the discharged residual amount is not
logged.
125
Display calibratable weight
Displays the content of the calibratable weight
value instead of the content of totalizing memory 1.
6-134
Executable
in following
operating
states
No weighing
cycle
All
No weighing
cycle
No weighing
cycle
Weighing cycle
All