Toshiba TOSVERT VF-AS3 Instruction Manual page 414

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 34. 7
<F709: Hold function of standard mode>
■ Function
The display in [Standard mode] can be held.
4
■ Parameter setting
4
Title
F709
6
■ Selecting a setting value
0: Real time
The contents selected with <F710: Standard mode display> are displayed.
9
1: Peak hold
2: Minimum hold
For peak hold values and minimum hold values, the maximum/minimum values in each operation
cycle are displayed.
• When the motor is at a standstill, the values monitored last are held as they were until the motor is
started the next time.
• The maximum and minimum values monitored after power is on are always displayed whether the
motor is running or at a standstill.
Reference
6. [Advanced] How to use parameters
Holding display in [Standard mode]
Parameter name
Hold function of standard
mode
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
F709 : Standard mode hold
0: Real time
1: Peak hold
2: Minimum hold
Adjustment range
0: Real time
1: Peak hold
2: Minimum hold
6-172
E6582062
STOP
0.0Hz
14:13
Default setting
0