Toshiba TOSVERT VF-AS3 Instruction Manual page 175

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

5. 2. 3
Setting the output frequency limit
(1)
Setting the maximum frequency of the inverter
<FH: Maximum frequency>
Basic parameter
■ Function
Set the maximum value of the frequency output from the inverter.
This frequency is also the criteria of acceleration and deceleration time.
■ Parameter setting
Title
Parameter name
FH
Maximum frequency
*1
Depending on the setup menu. Refer to [5. 3. 10].
The value of <FH> should be equal or greater than that of <VL>.
■ Guideline for the setting
Set the maximum frequency suited for the rating of the motor and load.
• Set <FH: Maximum frequency> after stopping the inverter. You cannot set it during run.
• When increasing the value of <FH: Maximum frequency>, you should also set the corresponding
Memo
value of <UL: Upper limit frequency> as required. --> Refer to the following "Setting the upper
and lower limits of the output frequency".
30.0 - 590.0
Output frequency (Hz)
80 Hz
60 Hz
0
5-9
STOP
FH
:Maximum frequency
Min: 30.0
X1000
X100
Adjustment range
When <FH> = 80 Hz
When <FH> = 60 Hz
Frequency command
signal (%)
100%
5. [Fundamental operation] How to use parameters
E6582062
0.0Hz
15:08
80.0
Hz
Max: 590.0
X10
X1
Default
Unit
setting
Hz
*1
80.0
3
4
5
9