B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 46)
ADDR
REGISTER NAME
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
B
AA81
IEC 61850 GSSE Function (GsEna)
AA82
IEC 61850 GSSE ID
AAA3
IEC 61850 GOOSE Function (GoEna)
AAA4
IEC 61850 GSSE Destination MAC Address
AAA7
IEC 61850 Standard GOOSE ID
AAC8
IEC 61850 Standard GOOSE Destination MAC Address
AACB
IEC 61850 GOOSE VLAN Transmit Priority
AACC
IEC 61850 GOOSE VLAN ID
AACD
IEC 61850 GOOSE ETYPE APPID
AACE
Reserved (2 items)
IEC 61850 Server Configuration (Read/Write Settings/Commands)
AAD0
TCP Port Number for the IEC 61850 / MMS Protocol
AAD1
IEC 61850 Logical Device Name
AAE1
IEC 61850 Logical Device Instance
AAF1
IEC 61850 LPHD Location
AB19
Include non-IEC 61850 Data
AB1A
IEC 61850 Server Data Scanning Function
AB1B
Command to Clear XCBR1 OpCnt (operation counter)
AB1C
Command to Clear XCBR2 OpCnt (operation counter)
AB1D
Reserved (15 items)
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00
Number of analog points in GGIO4
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10
IEC 61850 GGIO4 analog input 1 value
AF11
IEC 61850 GGIO4 analog input 1 deadband
AF13
IEC 61850 GGIO4 analog input 1 minimum
AF15
IEC 61850 GGIO4 analog input 1 maximum
AF17
...Repeated for IEC 61850 GGIO4 analog input 2
AF1E
...Repeated for IEC 61850 GGIO4 analog input 3
AF25
...Repeated for IEC 61850 GGIO4 analog input 4
AF2C
...Repeated for IEC 61850 GGIO4 analog input 5
AF33
...Repeated for IEC 61850 GGIO4 analog input 6
AF3A
...Repeated for IEC 61850 GGIO4 analog input 7
AF41
...Repeated for IEC 61850 GGIO4 analog input 8
AF48
...Repeated for IEC 61850 GGIO4 analog input 9
AF4F
...Repeated for IEC 61850 GGIO4 analog input 10
AF56
...Repeated for IEC 61850 GGIO4 analog input 11
AF5D
...Repeated for IEC 61850 GGIO4 analog input 12
AF64
...Repeated for IEC 61850 GGIO4 analog input 13
AF6B
...Repeated for IEC 61850 GGIO4 analog input 14
AF72
...Repeated for IEC 61850 GGIO4 analog input 15
AF79
...Repeated for IEC 61850 GGIO4 analog input 16
AF80
...Repeated for IEC 61850 GGIO4 analog input 17
AF87
...Repeated for IEC 61850 GGIO4 analog input 18
AF8E
...Repeated for IEC 61850 GGIO4 analog input 19
AF95
...Repeated for IEC 61850 GGIO4 analog input 20
AF9C
...Repeated for IEC 61850 GGIO4 analog input 21
AFA3
...Repeated for IEC 61850 GGIO4 analog input 22
B-38
RANGE
UNITS
1 to 60
0 to 1
---
0 to 1
---
---
---
0 to 7
0 to 4095
0 to 16383
0 to 1
1 to 65535
---
---
---
0 to 1
0 to 1
0 to 1
0 to 1
4 to 32
---
0.001 to 100
–1000000000000 to
1000000000000
–1000000000000 to
1000000000000
D30 Line Distance Relay
APPENDIX B
STEP
FORMAT
s
1
F001
---
1
F102
---
---
F209
---
1
F102
0 (Disabled)
---
---
F072
---
---
F209
"GOOSEOut"
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F213
---
---
F213
---
---
F204
---
1
F102
0 (Disabled)
---
1
F102
0 (Disabled)
---
1
F126
---
1
F126
---
4
F001
---
---
F600
%
0.001
F003
---
0.001
F060
---
0.001
F060
DEFAULT
60
1 (Enabled)
"GSSEOut"
0
0
4
0
0
0
102
"IECName"
"LDInst"
"Location"
0 (No)
0 (No)
4
0
100000
0
1000000
GE Multilin