B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 46)
ADDR
REGISTER NAME
7F31
Auxiliary Overvoltage 1 Signal Source
7F32
Auxiliary Overvoltage 1 Pickup
7F33
Auxiliary Overvoltage 1 Pickup Delay
7F34
Auxiliary Overvoltage 1 Reset Delay
7F35
Auxiliary Overvoltage 1 Block
B
7F36
Auxiliary Overvoltage 1 Target
7F37
Auxiliary Overvoltage 1 Events
7F38
Reserved (8 items)
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
7F61
Auxiliary Undervoltage 1 Signal Source
7F62
Auxiliary Undervoltage 1 Pickup
7F63
Auxiliary Undervoltage 1 Delay
7F64
Auxiliary Undervoltage 1 Curve
7F65
Auxiliary Undervoltage 1 Minimum Voltage
7F66
Auxiliary Undervoltage 1 Block
7F67
Auxiliary Undervoltage 1 Target
7F68
Auxiliary Undervoltage 1 Events
7F69
Reserved (7 items)
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0A
Digital Element 1 Pickup Delay
8A0C
Digital Element 1 Reset Delay
8A0E
Digital Element 1 Block
8A0F
Digital Element 1 Target
8A10
Digital Element 1 Events
8A11
Digital Element 1 Pickup LED
8A12
Reserved (2 items)
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
8AA0
...Repeated for Digital Element 9
8AB4
...Repeated for Digital Element 10
8AC8
...Repeated for Digital Element 11
8ADC
...Repeated for Digital Element 12
8AF0
...Repeated for Digital Element 13
8B04
...Repeated for Digital Element 14
8B18
...Repeated for Digital Element 15
8B2C
...Repeated for Digital Element 16
8B40
...Repeated for Digital Element 17
B-32
RANGE
UNITS
0 to 5
0 to 3
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 1
0 to 3
0 to 65535
0 to 2
0 to 1
0 to 65535
---
---
0 to 1
---
0 to 65535
0 to 999999.999
0 to 999999.999
0 to 65535
0 to 2
0 to 1
0 to 1
---
D30 Line Distance Relay
APPENDIX B
STEP
FORMAT
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
---
1
F111
0 (Definite Time)
pu
0.001
F001
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
---
1
F001
Hz
---
F001
---
---
F300
---
1
F102
---
---
F203
"Dig Element 1"
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
0 (Self-reset)
---
1
F102
---
1
F102
---
---
F001
DEFAULT
0 (SRC 1)
300
100
100
0
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
700
100
100
0
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0
0
0 (Disabled)
1 (Enabled)
0
GE Multilin